Summary
With the enactment of the Kigali amendment, the HFCs are falling into disuse and HFOs are proposed to be studied for replacement. R1233zd(E) as a new HTHP working fluid with low GWP has yet to be further developed. The HTHP is an ideal replacement of boiler to supply heat in industry. However, the construction of megawatt unit usually has a huge investment and may not achieve the desired results. Therefore, a mathematical model is imperative to conduct the performance prediction. This paper proposed a model and it can effectively verify the feasibility of the megawatt R1233zd(E) HTHP system, which recovers 60-80°C waste heat and outputs 100-160? pressured water. The conditions of condensation temperature from 90-160°C with temperature lift of 50K, were calculated and the COP changed in 3.0-3.8. When evaporating at 60°C and condensing at 110°C, the heat capacity was up to 1.95MW with COP over 3.8. From the results, R1233zd(E) is a reliable refrigerant for both high temperature output and high system efficiency, which will be a direction for future experiments.
Available documents
Format PDF
Pages: 10 p.
Available
Free
Details
- Original title: Modeling of Megawatt R1233zd(E) High Temperature Heat Pump System.
- Record ID : 30030006
- Languages: English
- Subject: HFCs alternatives
- Source: 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Publication date: 2021/08/31
Links
See other articles from the proceedings (198)
See the conference proceedings
Indexing
-
Themes:
Industrial heat pumps;
HFO et HCFO - Keywords: High temperature; Heat pump; R1233zd(E); Modelling; COP; Calculation; Performance
-
Industrial high temperature heat pump for steam...
- Author(s) : HAMACHER T.
- Date : 2023/05/15
- Languages : English
- Source: 14th IEA Heat Pump Conference 2023, Chicago, Illinois.
- Formats : PDF
View record
-
Thermal dynamic analysis of low GWP alternative...
- Author(s) : YANG M., ZHANG H., QIN Y., NONG K.
- Date : 2023/04/05
- Languages : English
- Source: 3rd IIR conference on HFO Refrigerants and low GWP Blends. Shanghai, China.
- Formats : PDF
View record
-
High temperature heat pump using HFO and HCFO r...
- Author(s) : ARPAGAUS C., KUSTER R., PRINZING M., et al.
- Date : 2019/08/24
- Languages : English
- Source: Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
View record
-
Experimental comparison of R1224yd(Z) and R1233...
- Author(s) : ARPAGAUS C., BERTSCH S.
- Date : 2021/08/31
- Languages : English
- Source: 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Formats : PDF
View record
-
Performance analysis for R1234ze(E) using in va...
- Author(s) : ZHAO P., JIA L., ZHOU J., QU B., KE Y., WANG R.
- Date : 2023/04/05
- Languages : English
- Source: 3rd IIR conference on HFO Refrigerants and low GWP Blends. Shanghai, China.
- Formats : PDF
View record